ADH50 Contactor Relay
Features
1, high-strength epoxy resin sealing, no risk of arc leakage, ensuring no fire or explosion during life;
2, potting nitrogen-based gas, effectively preventing contact oxidation and burning, low and stable contact resistance, contact part can meet IP67 protection level;
3, 50A 25 ℃ long-term current carrying capacity;
4, insulation resistance up to 100MΩ(1000VDC), withstand voltage between contact and coil 3.5kV;
5, in line with IEC 60664-1,GB/T14048.1 and GB/T14048.4 requirements;
6, in line with RoHs(2002/95/EC) requirements;
7, safety certification: CE;
Keyword: ADH50 Contactor Relay
Product Details
For a long time, the company has won extensive trust and support from customers with its ever-increasing innovation capabilities, stable quality assurance capabilities, professional customization capabilities, timely delivery capabilities and high-quality after-sales service system. Volkswagen, Komatsu, Dongfeng, GOODWINCH, TMAX and other major companies have formed close strategic partnerships.The company has strong research and development capabilities, precise production equipment, advanced production technology, sophisticated testing equipment and a million-level purification workshop. There are more than 20 series of products with a total of more than 1000 specifications, such as high and low voltage DC contactors, power switches, connectors, etc, it is widely used by customers in new energy electric vehicles and supporting charging stations and charging piles, photovoltaic and wind power generation systems, energy storage power stations, battery packs, electric forklifts, electric winches, battery cars, electric locomotives, UPS, medical equipment, communication power supplies, Inverter, power backup and other fields, and are exported to Asia, Europe and America.Today, all Okai people are refreshed and enterprising! Facing the market and customers, we have only one promise: Okay, let the electricity be in control!
A contactor relay, also known as an electrical relay or simply a relay, is an essential component in electrical systems. It is designed to control the flow of electricity by opening or closing contacts based on the presence or absence of an electrical signal.
1. Function: A contactor relay serves as a switch that allows or interrupts the electrical current in a circuit. It typically consists of an electromagnet, which when energized, creates a magnetic field that pulls the contacts together, allowing the current to flow. When the electromagnet is de-energized, the contacts spring back into their resting position, breaking the circuit and stopping the current.
2. Applications: Contactors relays are widely used in various industries and applications. They are commonly found in HVAC systems, motor control circuits, lighting control systems, and industrial machinery. Contactors are particularly useful in controlling high-power loads or multiple electrical circuits simultaneously. They can handle significant voltages and currents, making them suitable for heavy-duty applications.
3. Advantages: Contactors relays offer several advantages over traditional mechanical switches. Since they are operated by an electromagnetic mechanism, they provide faster response times and have a longer lifespan compared to mechanical switches. Additionally, contactors can be remotely controlled, allowing for automation and integration with other systems. They also feature arc suppression technology, which helps prevent arcing and ensures reliable operation.
In summary, contactor relays play a crucial role in controlling electrical current in a wide range of applications. They offer efficient switching capabilities, high reliability, and the ability to handle high-power loads. Their versatility and remote control capabilities make them an indispensable component in modern electrical systems.
| main load contact parameter | |
| contact form | 1K(1NO) |
| contact polarity | non-polarity |
| contact resistance | ≤ 0.5 mΩ(at 50A) |
| maximum switching voltage | 900VDC |
| maximum breaking current | 800A(320VDC) once |
|
electrical durability a |
1000 times (900VDC,50A) |
| 3000 times (750VDC,50A) | |
| 9000 times (450VDC,50A) | |
| Mechanical durability | 300000 times |
|
Electrical durability B |
50A, continuous |
| 130A,60min | |
| 180A,5min | |
| 300A,30S | |
| performance parameters (at23 c) | ||
| pull-in voltage | ≤ 70% Us | |
| release voltage | <40% Us,>5% Us | |
| pull-in time | ≤ 25ms | |
| contact bounce time | ≤ 5ms | |
| release time | ≤ 10ms | |
|
dielectric withstand voltage |
main contact | 3500VDC 1min |
| Main Contact and Coil | 3500VDC 1min | |
|
Insulation Resistance |
Initial State | 100 MΩ 1min c |
| Electrical Life | 50MΩ 1min | |
|
Impact |
stability | 20g (energization) |
| strength | 50g | |
| vibration | 10g,10 to 500Hz,1/2 Sine Wave (Power on) | |
| Humidity | 5% ~ 95% RH | |
| Temperature | -40 C ~ 85 C | |
| Load End Lead End Type | M4 Internal Thread | |
| Weight | About 230g | |
| overall dimensions | 55mm * 42mm * 64mm | |
| auxiliary contact parameters | |
| auxiliary contact form | 1K/1B(1NO/1NC) |
| auxiliary contact rated current | 5A |
| Auxiliary Contact Maximum Breaking Voltage | 120VDC |